Not sure this is the right bore? Work it out from your peak and minimum flow — the sizing calculator needs two numbers.

Engineering tool · free, no sign-up

Water meter sizing calculator


Give us the peak flow you must measure and the smallest flow you must still see, and this works out the bore, the Q3, and which range ratio puts your minimum inside the accuracy band. It uses the relationships printed in the meter documentation, and the published flow tables of this range.

The highest flow the meter will see continuously. Not a surge.
Night flow, leakage threshold, or the smallest billed draw. Leave empty if you only need the top end.
On an existing line, pick the bore you already have.

Every figure below comes from the published specification tables of this range. Where a bore has no printed Q3, it is Q4 ÷ 1.25, which is the relationship the documentation states.

How the numbers relate

Four flows define any meter, and three of them are fixed once you choose Q3 and the ratio. This is the arithmetic the calculator runs:

Q3 — rated flowThe flow the meter is designed to run at continuously
Q4 — overload flowQ4 = 1.25 × Q3. The meter has to survive it briefly
R — range ratioR = Q3 ÷ Q1. Chosen when the meter is ordered
Q1 — minimum flowQ1 = Q3 ÷ R. The bottom of the accuracy band
Q2 — transitional flowQ2 = 1.6 × Q1. Between Q1 and Q2 the tolerance is wider

Class 2 accuracy means ±5% between Q1 and Q2, and ±2% between Q2 and Q4. That is why the ratio matters more than the bore: at a fixed Q3, going from R250 to R500 halves Q1 and moves your leakage threshold into the ±2% band.

How to size a water meter in three steps

  1. Fix Q3 from the peak flow. Take the highest flow the meter will see continuously — not a surge — and choose the bore whose Q3 is at or above it. Q4, the overload, is 1.25 times Q3 and only has to be survived briefly.
  2. Fix R from the smallest flow you have to see. Q1 is Q3 divided by R, so R = Q3 ÷ Q1. Choose the smallest published ratio that puts Q1 at or below your minimum — that is the night flow, the leakage threshold or the smallest draw you bill.
  3. Check the pair against the bore. If no ratio published for that bore reaches your minimum, the bore is too large for what you need to see. Stepping down a bore lowers Q3 and brings Q1 down with it.

If the line is a solar thermal loop rather than a mains supply — glycol, high temperature, a pump curve instead of a pressure main — the four typical cases are worked through in our sizing guide for solar thermal flow meters.

What Q1, Q2, Q3 and Q4 mean

Q1 — minimum flow
The lowest flow at which the meter still meets its accuracy class. Below Q1 the reading is not guaranteed, which is why a leakage programme is really a question about Q1.
Q2 — transitional flow
The boundary between the two tolerances. Between Q1 and Q2 the permitted error is wider; from Q2 upwards it is tighter.
Q3 — permanent flow
The rated flow the meter is designed to run at continuously. This is the number to match against normal operation, not Q4.
Q4 — overload flow
1.25 times Q3. The meter has to survive it for short periods without damage, but running at Q4 as normal operation is a sizing error, not a margin.
R — range ratio
Q3 divided by Q1. A single number that tells you how far down the meter can still measure. It is fixed when the meter is ordered, not in the field.

Published flow at each bore

BoreQ3 m³/hQ4 m³/hRatios offeredBasis
DN152.503.125R80–R500 · R400–R1000 by familyQ4 printed; Q3 = Q4 ÷ 1.25
DN204.005.000R80–R500 · R400–R1000 by familyQ4 printed; Q3 = Q4 ÷ 1.25
DN256.307.875R80–R500 · R400–R1000 by familyQ4 printed; Q3 = Q4 ÷ 1.25
DN3210.012.50R160–R630Q4 printed; Q3 = Q4 ÷ 1.25
DN4016.020.00R160–R630Q4 printed; Q3 = Q4 ÷ 1.25
DN5025.031.25R160–R630 · R250–R500 flanged · R400 standardQ3 printed (DN50 and LXCY-50 pages)
DN6540.050.00R250 / R400 / R500Q3 printed; R400 standard
DN8063.078.75R250 / R400 / R500Q4 printed in the DN50–DN150 family table
DN100100125.0R250 / R400 / R500Q4 printed in the family table
DN125160200.0R250 / R400 / R500Q4 printed in the family table
DN150250312.5R250 / R400 / R500Q4 printed in the family table

Straight pipe and pressure loss

These are the two questions engineers ask immediately after sizing, and they are the two we can only answer to the extent they are published:

Questions this tool raises

Should Q3 match my peak flow, or exceed it?
Q3 is the rated flow the meter runs at continuously, so it should sit at or above the highest flow you expect to see for long periods. Q4, which is 1.25 times Q3, is the overload the meter has to survive briefly. Sizing Q3 below your normal peak puts the meter in overload as routine operation.
Why does the ratio change the price more than the bore?
At a fixed Q3, a higher ratio means a lower Q1, which is harder to hold inside ±2% and requires individual wet calibration. R400 is the standard configuration; R250 and R500 are ordered for a reason, usually a leakage programme that needs to see night flow.
My minimum flow is below Q1 for every ratio listed. Now what?
Then the bore is too large for what you need to see. Either step down a bore and accept a lower Q3, or keep the bore and accept that the smallest flows sit outside the accuracy band. Tell us both numbers and we will say which compromise is cheaper for your tariff.
Does the calculator account for viscosity or temperature?
No. It sizes on the flow relationships and the published tables only. Temperature class is T30 as standard with T50 and T70 by order, and the accuracy figures above are the cold-water figures stated as ±2% between 0.1 and 30 °C on the DN50 page.
Can I use the result directly in a tender document?
Use it to choose the bore and the ratio. For the document itself, take the figures from the datasheet PDF of the model you select, and state the ratio you want, because R is fixed at order.

New to the flow ratings? Q3, Q4 and the DN you actually need explains what each number decides — and why oversizing a meter costs resolution at night — before you enter anything here.

Next step

Send the two numbers instead

Give us the peak flow, the smallest flow you must see and the line size. We come back with the bore, the ratio, the datasheet for that model and a price — no form to fill in first.