LXCY-15~50 Remote Ultrasonic Water Meter

A transit-time ultrasonic meter for residential and light-commercial lines from DN15 to DN50. No moving parts in the water path, Class 2 accuracy that holds at low flow, IP68 sealing, and one communication module pre-installed per meter — RS485 / M-BUS, or 2G / 4G Cat.1 / NB-IoT / LoRaWAN / Wi-SUN.

DN15–DN50 bore range Class 2 ISO 4064 IP68 protection 3.6 V lithium battery R400 on DN32–DN50
LXCY-15 remote ultrasonic water meter, DN15 body with union connections
DN15, union ends
How it measures

Transit time, in both directions


Two transducers send ultrasonic pulses with and against the flow. The difference in travel time gives the velocity, and the meter integrates it into volume — in both directions, so backflow and tampering are metered rather than hidden.

Measuring principleTransit-time ultrasonic, bidirectional; single-channel for DN≤40
AccuracyClass 2, designed and manufactured to ISO 4064; factory inspection to ISO/IEC 17025
Range ratioR200 on DN15–DN25; R400 on DN32–DN50. R80 / 100 / 160 / 315 / 400 / 500 on DN15–DN25 and R160 / 315 / 500 / 630 on DN32–DN50 by custom order
Body materialsStainless steel, brass or engineering plastic (DN15–DN25); stainless steel, copper or engineering plastic (DN32–DN50)
InstallationHorizontal or vertical, no accuracy loss; flow-field sensitivity U0/D0 — no straight-pipe run required under normal conditions
SealingIP68, whole meter — it can stay submerged
AlarmsLeak, reverse flow, tampering, damaged electronic seal, empty pipe, low battery, abnormal water temperature, transducer fault
Flow parameters

Rated flow by bore


Values as published in the LXCY-15~25 and LXCY-32~50 manuals. Q4 is the overload flow the meter must survive briefly, Q3 the rated flow, Q1 the minimum flow inside the accuracy band.

Nominal boreQ4
m³/h
Q3
m³/h
Q2
L/h
Q1
L/h
R
Q3/Q1
Temp class
DN153.1252.52012.5200T30 / T50 / T70
DN205.0004.03220200T30 / T50 / T70
DN257.8756.350.425.2200T30 / T50 / T70
DN3212.510.04025400T30 / T50
DN4020.016.06440400T30 / T50
DN5031.2525.010062.5400T30 / T50

Maximum permissible error: ±5% in the low zone (Q1 ≤ Q < Q2); ±2% in the high zone (Q2 ≤ Q ≤ Q4) on DN15–DN25, and ±2% between 0.1 °C and 30 °C / ±3% above 30 °C on DN32–DN50.

DN50 is also built as a flanged meter in the LXCY-50~300 series — choose the connection you already have in the line.

Ratio options

Lower ratios on DN32–DN50


If the line needs a wider Q1 than R400 gives, the same body is available at R250 and R200. Only Q2 and Q1 move; Q3 and Q4 stay as listed above.

BoreRQ2
L/h
Q1
L/h
DN3225064.040.0
DN3220080.050.0
DN40250102.464.0
DN40200128.080.0
DN50250160.0100.0
DN50200200.0125.0
Physical & environmental

Where it can be installed


ParameterDN15–DN25DN32–DN50
Accuracy classClass 2Class 2
Temperature classT30 / T50 / T70T30 / T50
Operating temperature-25 °C to +55 °C (other ranges on request)-25 °C to +55 °C
Storage temperature—-25 °C to +55 °C
Relative humidity≤100 % RH (condensing version on request)—
Protection gradeIP68IP68
Working pressure1.0 MPa (PN10) standard; 1.6 MPa optional; 2.5 MPa on request1.6 MPa (PN16)
Pressure loss classΔp40Δp40
Environment classClass OClass O
EMC classE2E2
Reverse flowMeasured and totalledMeasured and totalled
Electronics & communication

One module per meter, chosen at order


Every meter leaves the factory with a single communication module fitted. Wired and wireless builds share the same register and the same alarm set.

Power supply3.6 V DC lithium battery
Battery life≥8 years on timed upload (reading every 20 min, upload every 12 h). The DN15–DN25 manual also states up to 10 years at 25 ±5 °C; expect less in weak-signal sites or at high alarm frequency.
Current consumptionSleep ≤18 µA; standby ≤1.8 mA; peak transmit ≤210 mA (DN15–DN25)
Wired interfacesRS-485 / M-BUS
Wireless interfaces2G / 4G Cat.1 / NB-IoT / LoRaWAN / Wi-SUN
Local interfaceInfrared port for on-site parameter setting and read-out
Display9-digit LCD with function symbols; cumulative flow, instantaneous flow, water temperature, operating hours, date/time, meter ID, software version, alarm code
ResolutionCumulative flow 0.0001 m³; instantaneous flow 0.0001 m³/h; temperature 0.01 °C
Totalising range0 – 999,999.999 m³
Data retentionHistorical data kept more than 10 years after power loss
Remote functionsRemote configuration, firmware update, scheduled upload, alarm push through the utility platform
Dimensions

Face-to-face length you can plan around


L is the meter body; L1 includes the standard union tailpieces and is the length to reserve in the line. All figures in millimetres.

DN15–DN25, union connection

BoreLL1HWSMeter threadUnion thread
DN151251651127545G3/4BR1/2
DN201251951187551G1BR3/4
DN251682251207559G1¼BR1

DN32–DN50, union connection

BoreLL1WHH1Thread
DN3223035096125212G1½B
DN4024537696134221G2B
DN5030041096138225G2½B

H1 is the overall height including the register. Dimensions are nominal and subject to normal casting tolerance — ask for the drawing before you cut pipe.

Ordering

What to specify


Five details decide the build. Send them together and the quotation comes back with a drawing, not with questions.

BoreDN15, 20, 25, 32, 40 or 50 — or the flow range you need to cover, and we will size it
RatioR200 on DN15–DN25 or R400 on DN32–DN50 as standard; R250 / R200 on DN32–DN50; other ratios by custom order
CommunicationRS485, M-BUS, 2G, 4G Cat.1, NB-IoT, LoRaWAN or Wi-SUN — one module per meter
BodyStainless steel, brass or engineering plastic; pressure rating PN10 / PN16 / PN25
TemperatureCold water T30, T50, or hot water T70 (DN15–DN25)
Questions we get asked

Before you specify


No. Flow-field sensitivity is U0/D0, so under normal conditions no straight-pipe run is required, and the meter installs horizontally or vertically without accuracy loss.

R200 on DN15–DN25 and R400 on DN32–DN50 as standard. R80, R100, R160, R315, R400 and R500 are available on DN15–DN25, and R160, R315, R500 and R630 on DN32–DN50; other ratios are a custom order.

Eight years or more on the stated duty — a reading every 20 minutes and an upload every 12 hours. The DN15–DN25 manual also states up to 10 years at 25 ±5 °C, so the figure moves with the upload interval you configure.

Yes. The whole meter is IP68, so it can stay submerged. Historical data is retained for more than 10 years after a power loss, so an interruption does not reset the register.