A four-channel transit-time meter built as a flanged pipe section for distribution mains and plant rooms. Class 2 bidirectional measurement, 1.6 MPa body, IP68 sealing, and one communication module per meter — RS485 / M-BUS, or 2G / 4G Cat.1 / NB-IoT / LoRaWAN / Wi-SUN.

On DN50 and above the meter uses four measuring paths instead of one. Averaging four chords flattens the effect of an uneven velocity profile — the swirl and asymmetry you get downstream of a bend or a partly closed valve — so the reading stays stable on a real distribution main, not just on a test bench.
| Measuring principle | Transit-time ultrasonic, four-channel, bidirectional |
|---|---|
| Accuracy | Class 2, designed and manufactured to ISO 4064; factory inspection to ISO/IEC 17025 |
| Range ratio | R400 and R250 across the range; R50 / 63 / 80 / 100 / 125 / 160 / 315 / 500 / 630 / 800 by custom order |
| Body | Integral cast-iron flanges to ISO 4064; bolted both ends, so the meter drops into the line as a spool piece |
| Installation | Any orientation; flow-field sensitivity U0/D0 |
| Sealing | IP68, whole meter |
| Alarms | Empty pipe, reverse flow, leakage, low battery, transducer fault |
Q4 is the overload flow the meter must survive briefly, Q3 the rated flow. Both are identical at R400 and R250 — only the bottom of the accuracy band moves with the ratio.
| Model | Q4 m³/h | Q3 m³/h | Q1 at R400 L/h | Q1 at R250 L/h |
|---|---|---|---|---|
| DN50 | 50.0 | 40.0 | 100.0 | 160.0 |
| DN65 | 50.0 | 40.0 | 100.0 | 160.0 |
| DN80 | 78.75 | 63.0 | 157.5 | 252.0 |
| DN100 | 125.0 | 100.0 | 250.0 | 400.0 |
| DN125 | 200.0 | 160.0 | 400.0 | 640.0 |
| DN150 | 312.5 | 250.0 | 625.0 | 1000.0 |
| DN200 | 500.0 | 400.0 | 1000.0 | 1600.0 |
| DN250 | 787.5 | 630.0 | 1575.0 | 2520.0 |
| DN300 | 1250.0 | 1000.0 | 2500.0 | 4000.0 |
Q1 is the bottom of the accuracy band and follows the ratio you order: Q3 ÷ 400 for R400, Q3 ÷ 250 for R250, with Q2 = 1.6 × Q1 as set by ISO 4064. Tell us the ratio and the quotation states Q1 and Q2 for every bore.
Maximum permissible error: ±2 % between 0.1 °C and 30 °C, ±3 % above 30 °C, across Q2 ≤ Q ≤ Q4.
| Accuracy class | Class 2 |
|---|---|
| Temperature class | T30, T50 |
| Maximum allowable pressure | 1.6 MPa |
| Pressure loss class | Δp16 |
| Installation orientation | Arbitrary |
| Flow-field sensitivity | U0/D0 |
| Reverse flow | Measured and totalled |
| Environment class | Class O |
| Electromagnetic environment | E2 |
| Protection grade | IP68 |
| Flange standard | ISO 4064 integral cast-iron flanges; special specifications stated at order |
| Power supply | 3.6 V lithium battery |
|---|---|
| Battery life | ≥8 years on timed upload (reading every 20 min, upload every 12 h) |
| Wired interfaces | RS485 / M-BUS |
| Wireless interfaces | 2G / 4G Cat.1 / NB-IoT / LoRaWAN / Wi-SUN |
| Local interface | Infrared port for on-site debugging and parameter setting |
| Display | LCD with function symbols |
| Data retention | Historical data kept more than 10 years after power loss |
| Minimum / maximum reading | 0.1 L / 999,999.9999 m³, rolling over to 99,999,999.99 m³ |
L is the face-to-face length, W the flange outside diameter, H the overall height over the register. All figures in millimetres.
| Bore | L | W flange Ø | H | D1 bolt circle | Bolts |
|---|---|---|---|---|---|
| DN50 | 200 | 225 | 165 | 125 | 4 × M16 |
| DN65 | 200 | 230 | 185 | 145 | 4 × M16 |
| DN80 | 225 | 240 | 200 | 160 | 8 × M16 |
| DN100 | 250 | 250 | 220 | 180 | 8 × M16 |
| DN125 | 250 | 250 | 220 | 180 | 8 × M16 |
| DN150 | 300 | 310 | 285 | 240 | 8 × M20 |
| DN200 | 350 | 360 | 340 | 295 | 12 × M20 |
| DN250 | 450 | 410 | 395 | 350 | 12 × M20 |
| DN300 | 500 | 450 | 445 | 400 | 12 × M20 |
Dimensions and weights are for reference and subject to the actual product. Ask for the certified drawing before fabrication.
Bore and ratio set the hydraulics; the rest is connection and network.
| Bore | DN50, 65, 80, 100, 125, 150, 200, 250 or 300 — or give us peak and minimum flow and we will size it |
|---|---|
| Ratio | R400 or R250 as standard; other ratios by custom order |
| Communication | RS485, M-BUS, 2G, 4G Cat.1, NB-IoT, LoRaWAN or Wi-SUN — one module per meter |
| Pressure | 1.6 MPa (PN16) as standard; state the line rating if higher |
| Connection | ISO 4064 flanges; state any other drilling standard at order |
The nine questions buyers ask about this range — which diameters exist, how the U0/D0 straight-pipe rule applies, how much history the meter keeps and what changes against a mechanical unit — are answered in our DN50–DN300 bulk meter guide.
Measured and totalled. The meter is four-channel and bidirectional, so backflow appears in the register instead of being treated as zero.
1.6 MPa (PN16) as standard, with a pressure-loss class of Δp16. Tell us the line rating if it is higher.
Integral cast-iron flanges to ISO 4064, bolted at both ends, so the meter drops into the line as a spool piece. Any other drilling standard is stated at order.
A minimum reading of 0.1 L and a maximum of 999,999.9999 m³, rolling over to 99,999,999.99 m³. Historical data is kept for more than 10 years after a power loss.
Interface translated. Technical documents stay in English.